Goodrive100 inverters
Appendix C
IKR Aandrijven en Besturen
www.ikr-industries.nl
The inverter
Breaker
(
A
)
Breaker
(
A
)
The rated working current
of the contactor
(
A
)
GD100-7R5G-4
60
40
25
GD100-011G-4
78
63
32
GD100-015G/-4
105
63
50
C.5 Reactors
High current in the input power circuit may cause damage to the rectifying components. It is appropriate to
use AC reactor in the input side for the avoidance of high-voltage input of the power supply and
improvement of the power factors.
If the distance between the inverter and the motor is longer than 50m, frequent overcurrent protection may
occur to the inverter because of high leakage current caused by parasitic capacitance effects from the long
cables to the ground. In order to avoid the damage of the motor insulation, it is necessary to add reactor
compensation.
The power of the inverter
Input reactor
Output reactor
GD100-0R7G-4
ACL2-1R5-4
OCL2-1R5-4
GD100-1R5G-4
ACL2-1R5-4
OCL2-1R5-4
GD100-2R2G-4
ACL2-2R2-4
OCL2-2R2-4
GD100-004G-4
ACL2-004-4
OCL2-004-4