Goodrive100 inverters
Product overview
IKR Aandrijven en Besturen
www.ikr-industries.nl
3. Check that the control accuracy of the load is the same of the inverter.
4. Check that the incoming supply voltage is correspondent to the rated voltage of the inverter.
2.1.3 Environment
Check as followings before the actual installation and usage:
1. Check that the ambient temperature of the inverter is below 40
℃
. If exceeds, derate 3% for every
additional 1
℃
. Additionally, the inverter can not be used if the ambient temperature is above 50
℃
.
Note: for the cabinet inverter, the ambient temperature means the air temperature inside the cabinet.
2. Check that the ambient temperature of the inverter in actual usage is above -10
℃
. If not, add heating
facilities.
Note: for the cabinet inverter, the ambient temperature means the air temperature inside the cabinet.
3. Check that the altitude of the actual usage site is below 1000m. If exceeds, derate1% for every
additional 100m.
4. Check that the humidity of the actual usage site is below 90% and condensation is not allowed. If not,
add additional protection inverters.
5. Check that the actual usage site is away from direct sunlight and foreign objects can not enter the
inverter. If not, add additional protective measures.
6. Check that there is no conductive dust or flammable gas in the actual usage site. If not, add additional
protection to inverters.