Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
1:Opposite to the setting direction
P10 Group Simple PLC and multi-stage speed control
P10.00
Simple PLC
means
0: Stop after running once. The inverter has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After finish a
signal, the inverter will keep the running frequency and
direction of the last run.
2: Cycle running. The inverter will keep on running until
receiving a stop command and then, the system will stop.
0
○
P10.01
Simple PLC
memory
selection
0: Power loss without memory
1:Power loss memory
;
PLC record the running stage and
frequency when power loss.
0
○
P10.02
Multi-stage
speed 0
100.0% of the frequency setting corresponds to the Max.
Frequency P00.03.
When selecting simple PLC running, set P10.02~P10.33 to
define the running frequency and direction of all stages.
Note: The symbol of multi-stage determines the running
direction of simple PLC. The negative value means reverse
rotation.
Multi-stage speeds are in the range of --f
max
~f
max
and it can
be
Goodrive100 series inverters can set 16 stages speed,
selected by the combination of multi-stage terminals 1~4,
0.0%
○
P10.03
The running
time of stage 0
0.0s
○
P10.04
Multi-stage
speed 1
0.0%
○