Goodrive100 inverters
Communication protocol
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
0009H:pre-exciting
The address of the
communication n
setting value
2001H
Communication setting frequency(0~Fmax(unit:
0.01Hz))
W
2002H
PID given, range(0~1000, 1000 corresponds
to100.0% )
2003H
PID feedback, range(0~1000, 1000 corresponds
to100.0% )
W
2004H
Torque
setting
value
(-3000~3000,
1000
corresponds to the 100.0% of the rated current
of the motor)
W
2005H
The upper limit frequency setting during forward
rotation(0~Fmax(unit: 0.01Hz))
W
2006H
The upper limit frequency setting during reverse
rotation(0~Fmax(unit: 0.01Hz))
W
2007H
The upper limit torque of electromotion torque
(0~3000, 1000 corresponds to the 100.0% of
the rated current of the motor)
W
2008H
The
upper
limit torque of braking torque
(0~3000, 1000 corresponds to the 100.0% of
W