Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
frequency
equal to the maximum frequency.
Setting range:P00.05~P00.03 (Max. output frequency)
P00.05
Lower limit of
the running
frequency
The lower limit of the running frequency is that of the output
frequency of the inverter.
The inverter runs at the lower limit frequency if the set
frequency is lower than the lower limit one.
Note:
Max. output frequency ≥ Upper limit frequency ≥ Lower
limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the running
frequency)
0.00Hz
◎
P00.06
A frequency
command
selection
0:Keypad data setting
Modify the value of function code P00.10 (set the frequency
by keypad) to modify the frequency by the keypad.
1:Analog AI1 setting(corresponding keyap potentiometer)
2:Analog AI2 setting(corresponding terminal AI2)
3:Analog AI3 setting(corresponding terminal AI3)
Set the frequency by analog input terminals. Goodrive100
series inverters provide 3 channels analog input terminals as
the standard configuration, of which AI1 is in the ranghe of
0V~+10V
while
AI2
is
the
voltage/current
option
(0~10V/0~20mA) which can be shifted by jumpers; while AI3
is voltage input (-10V~+10V).
0
○
P00.07
B frequency
command
selection
1
○