Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P04.28
Keypad setting
voltage
The function code is the voltage digital set value when the
voltage setting channel is selected as “keypad selection”
The setting range:0.0%~100.0%
100.0%
○
P04.29
Voltage
increasing time
Voltage increasing time is the time when the inverter
accelerates from the output minimum voltage to the output
maximum voltage.
Voltage decreasing time is the time when the inverter
decelerates from the output maximum voltage to the output
minimum voltage.
The setting range:0.0~3600.0s
5.0s
○
P04.30
Voltage
decreasing
time
5.0s
○
P04.31
Output
maximum
voltage
Set the upper and low limit of the output voltage.
The setting range of P04.31:P04.32~100.0%(the rated
voltage of the motor)
The setting range of P04.32:0.0%~ P04.31(the rated voltage
of the motor)
100.0%
◎
P04.32
Output
minimum
voltage
0.0%
◎
P05 Group Input terminals
P05.00
HDI input type
0: HDI is high pulse input. See P05.49~P05.54
0
◎