Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P01.14
Switching
between
FWD/REV
rotation
Set the threshold point of the inverter:
0:Switch after 0 frequency
1:Switch after the starting frequency
0
◎
P01.15
Stopping
speed
0.00~100.00Hz
0.10 Hz
◎
P01.16
Detection of
stopping speed
0: Detect at the setting speed
1: Detect at the feedback speed(only valid for vector control)
0
◎
P01.17
Detection time
of the feedback
speed
When P01.16=1, the actual output frequency of the inverter is
less than or equal to P01.15 and is detected during the time
set by P01.17, the inverter will stop; otherwise, the inverter
stops in the time set by P01.24.
Setting range: 0.0~100.0 s (only valid when P01.16=1)
0.05s
◎
P01.18
Terminal
running
protection
selection when
powering on
When the running command channel is the terminal control,
the system will detect the state of the running terminal during
powering on.
0:The terminal running command is invalid when powering
on. Even the running command is detected to be valid during
powering on, the inverter won’t run and the system keeps in
the protection state until the running command is canceled
and enabled again.
0
○