Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.36
AI1 input filter
time
the sensitivity of the analog input
Note: AI1 supports 0~10V input and AI2 supports 0~10V or
0~20mA input, when AI2 selects 0~20mA input, the
corresponding voltage of 20mA is 5V. AI3 can support the
output of -10V~+10V.
The setting range of P05.32:0.00V~P05.34
The setting range of P05.33:-100.0%~100.0%
The setting range of P05.34:P05.32~10.00V
The setting range of P05.35:-100.0%~100.0%
The setting range of P05.36:0.000s~10.000s
The setting range of P05.37:0.00V~P05.39
The setting range of P05.38:-100.0%~100.0%
The setting range of P05.39:P05.37~10.00V
The setting range of P05.40:-100.0%~100.0%
The setting range of P05.41:0.000s~10.000s
The setting range of P05.42:-10.00V~P05.44
The setting range of P05.43:-100.0%~100.0%
The setting range of P05.44:P05.42~P05.46
The setting range of P05.45:-100.0%~100.0%
0.100s
○
P05.37
Lower limit of
AI2
0.00V
○
P05.38
Corresponding
setting of the
lower limit of
AI2
0.0%
○
P05.39
Upper limit of
AI2
10.00V
○
P05.40
Corresponding
setting of
the upper limit
of AI2
100.0%
○
P05.41
AI2 input filter
time
0.100s
○
P05.42
Lower limit of
AI3
-10.00V
○