Function
code
Name
Detailed instruction of parameters
Default
value
Modify
1: The terminal running command is valid when powering on.
If the running command is detected to be valid during
powering on, the system will start the inverter automatically
after the initialization.
Note:
this function should be selected with cautions, or
serious result may follow.
P01.19
The running
frequency is
lower than the
lower limit one
(valid if the
lower limit
frequency is
above 0)
This function code determines the running state of the
inverter when the set frequency is lower than the lower-limit
one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set frequency is lower
than the lower-limit one.if the set frequency is above the
lower limit one again and it lasts for the time set by P01.20,
the inverter will come back to the running state automatically.
0
◎
P01.20
Hibernation
restore delay
time
This function code determines the Hibernation delay time.
When the running frequency of the inverter is lower than the
lower limit one, the inverter will pause to stand by.
When the set frequency is above the lower limit one again
and it lasts for the time set by P01.20, the inverter will run
automatically.
Note:
The time is the total value when the set frequency is
0.0s
○