Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
zone
power. The motor will enter into the weakening state when
the motor runs at rated speed. Change the weakening curve
by modifying the weakening control coefficienct. The bigger
the weakening control coefficienct is, the steeper the weak
curve is.
The setting range of P03.22:0.1~2.0
The setting range of P03.23:10%~100%
P03.23
The lowest
weakening
point in
Constant
power zone
50%
○
P03.24
Max. voltage
limit
P03.24 set the Max. Voltage of the inverter, which is
dependent on the site situation.
The setting range:0.0~120.0%
100.0%
◎
P03.25
Pre-exciting
time
Pre-activate the motor when the inverter starts up. Build up a
magnetic field inside the inverter to improve the torque
performance during the starting process.
The setting time:0.000~10.000s
0.300s
○
P04 Group V/F control
P04.00
Motor 1V/F
curve setting
These function codes define the V/F curve of Goodrive100
motor 1 to meet the need of different loads.
0:Straight line V/F curve
;
applying to the constant torque
load
1:Multi-dots V/F curve
0
◎