Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
0: No check (N,8,1)for RTU
1:Odd check (E,8,1)for RTU
2:Even check (O,8,1)for RTU
3:No check (N,8,2)for RTU
4: Odd check (E,8,2)for RTU
5:Even check(O,8,2)for RTU
P14.03
Communicatio
n answer
delay
0~200ms
It means the interval time between the interval time when the
drive receive the data and sent it to the upper monitor. If the
answer delay is shorter than the system processing time,
then the answer delay time is the system processing time, if
the answer delay is longer than the system processing time,
then after the system deal with the data, waits until achieving
the answer delay time to send the data to the upper monitor.
5
○
P14.04
Communicatio
n overtime fault
time
0.0(invalid),0.1~60.0s
When the function code is set as 0.0, the communication
overtime parameter is invalid.
When the function code is set as non-zero, if the interval time
between two communications exceeds the communication
overtime, the system will report “485 communication faults”
(CE).
Generally, set it as invalid; set the parameter in the
0.0s
○