Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
starting
power. The DC braking current before starting means the
percentage of the rated current of the inverter.
The setting range of P01.03: 0.0~150.0%
The setting range of P01.04: 0.0~50.0s
P01.05
ACC/DEC
selection
The changing mode of the frequency during start-up and
running.
0:Linear type
The output frequency increases or decreases linearly.
1:Reserved
0
◎
P01.08
Stop selection
0:Decelerate to stop: after the stop command becomes valid,
the inverter decelerates to decrease the output frequency
during the set time. When the frequency decreases to 0, the
inverter stops.
1:Coast to stop: after the stop command becomes valid, the
inverter ceases the output immediately. And the load coasts
to stop at the mechanical inertia.
0
○
P01.09
Starting
frequency of
DC braking
Starting frequency of DC braking: start the DC braking when
running frequency reaches starting frequency determined by
P1.09.
Waiting time before DC braking: Inverters blocks the output
before starting the DC braking. After this waiting time, the DC
braking will be started so as to prevent over-current fault
0.00Hz
○
P01.10
Waiting time
before DC
braking
0.0s
○