Goodrive100 inverters
Fault tracking
IKR Aandrijven en Besturen
www.ikr-industries.nl
Checking part
Checking item
Checking method
Criterion
expansion.
Ensure the safety valve is in
the right place.
Estimate the usage
time according to
the maintenance or
measure the static
capacity.
NA
If necessary, measure the
static capacity.
Measure
the
capacity
by
instruments.
The static capacity
is above or equal to
the original value
*0.85.
Resistors
Ensure whether there is
replacement
and
splitting
caused by overheating.
Smelling and visual
examination
NA
Ensure that there is no
offline.
Visual examination
or
remove
one
ending to coagulate
or
measure
with
multimeters
The resistors are in
±10%
of
the
standard value.
Transformers and
reactors
Ensure there is no abnormal
vibration, noise and smelling,
Hearing,
smelling
and
visual
examination
NA
Electromagnetism
Ensure whether there is
vibration
noise
in
the
Hearing
NA