Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Note:
Multi-stage speed given, it is realized by setting P10
group parameters.
P09.01
Keypad PID
preset
When P09.00=0, set the parameter whose basic value is the
feedback value of the system.
The setting range:-100.0%~100.0%
0.0%
○
P09.02
PID feedback
source
Selection
Select the PID channel by the parameter.
0:Analog channel AI1 feedback
1:Analog channel AI2 feedback
2:Analog channel AI3 feedback
3:High speed HDI feedback
4:MODBUS communication feedback
5~7:Reserved
Note: The given channel and the feedback channel can not
coincide, otherwise, PID can not control effectively.
0
○
P09.03
PID output
feature
selection
0: PID output is positive: When the feedback signal exceeds
the PID given value, the output frequency of the inverter will
decrease to balance the PID. For example, the strain PID
control during wrapup
1: PID output is negative: When the feedback signal is
0
○