Goodrive100 inverters
Product overview
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
Specification
Relay output
2 channels programmable relay output
RO1A NO, RO1B NC, RO1C common terminal
RO2A NO, RO2B NC, RO2C common terminal
Contactor capability: 3A/AC250V
Others
Mountable method
Wall mountable and flange mountable
Temperature of the
running environment
-10~50
℃
, derate above 40
℃
Average non-fault time
2 years (25
℃
ambient temperature)
Protective degree
IP20
Cooling
Air-cooling
Braking unit
Embedded
EMC filter
Built-in C3 filter: meet the degree requirement of
IEC61800-3 C3
External filter:meet the degree requirement of IEC61800-3
C2