Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
above the lower limit one.
Setting range: 0.0~3600.0s (valid when P01.19=2)
P01.21
Restart after
power off
This function can enable the inverter start or not after the
power off and then power on.
0: Disabled
1: Enabled, if the starting need is met, the inverter will run
automatically after waiting for the time defined by P01.22.
0
○
P01.22
The waiting
time of restart
after power off
The function determines the waiting time before the
automatic running of the inverter when powering off and then
powering on.
Setting range: 0.0~3600.0s (valid when P01.21=1)
1.0s
○
P01.23
Start delay
The function determines the brake release after the running
command is given, and the inverter is in a stand-by state and
0.0s
○