Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
decreasing and surge.
The manufacturer has set a reasonable carrier frequency
when the inverter is in factory. In general, users do not need
to change the parameter.
When the frequency used exceeds the default carrier
frequency, the inverter needs to derate 20% for each
additional 1k carrier frequency.
Setting range:1.0~15.0kHz
P00.15
Motor
parameter
autotuning
0:No operation
1:Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning when high
control accuracy is needed.
2:Static autotuning
It is suitable in the cases when the motor can not de-couple
form the load. The antotuning for the motor parameter will
impact the control accuracy.
0
◎
P00.16
AVR function
selection
0:Invalid
1:Valid during the whole prodecure
The auto-adjusting function of the inverter can cancel the
impact on the output voltage of the inverter because of the
1
○