4. Parameter Code List
38
Code
Function name
Setting range
Initial
data
Change
mode
on run
Page
o024
Over-torque level 3
0~200[%]
100
○
117
o025
Over-torque level 4
0~200[%]
100
○
117
o026
Overload advance notice level 1
Rated current*0.0~2.0[times]
1.0
○
116
o027
Overload advance notice level 2
Rated current *0.0~2.0[times]
1.0
○
116
o028
RUN/ON time-over setting
0~9999
0
○
118
o029
PID deviation setting level
0.0~100.0[%]
3.0
○
116
o030
Zero speed detection level setting
0.00~99.99[Hz]
0.00
○
119
o031
AL relay output definition
5
○
109
o032
RN relay output definition
Refer to the intelligent output setting
0
○
109
o033
AL relay output selection
0
○
110
o034
RN relay output selection
Intelligent output contactor setting
0 : N.O, 1: N.C
0
○
110
Table 4- 8 Intelligent output terminal setting (o-group)
4.2.9
Advanced control function setting (C-group)
Code
Function name
Setting range
Initial
data
Change
mode
on run
Page
C002
V/f stability adjust
0.0~300.0[%]
100
○
123
C003
Torque boost selection
0(Manual), 1(Automatic)
0
ⅹ
123
C203
Torque boost selection,
2
nd
motor
0(Manual), 1(Automatic)
0
ⅹ
C004
Manual torque boost value
0.0~20.0[%]
1.0
○
123
C204
Manual torque boost value,
2
nd
motor
0.0~20.0[%] 1.0
○
92
C005
Manual torque boost break point
0.0~50.0[%]
5.0
○
123
C205
Manual torque point boost
frequency, 2
nd
motor
0.0~50.0[%] 5.0
○
92
C006
Torque limit selection
0(4 Guad mode), 1(TER. OPR),
2(Analog IN), 3(OPT1), 4(OPT2)
0
○
125
C007
Torque limit 1
0~200[%]
200
○
125
C008
Torque limit 2
0~200[%]
200
○
125
C009
Torque limit 3
0~200[%]
200
○
125
C010
Torque limit 4
0~200[%]
200
○
125
C011
Torque LAD Stop selection
0(Disable), 1(Enable)
0
○
125
C012
Braking control function selection 0(Disable),
1(Enable)
0
○
126
C013
Waiting time for braking
releasing
confirmation
0.00~5.00[sec] 0.00
○
126
C014
Waiting time for acceleration
0.00~5.00[sec]
0.00
○
126
C015
Waiting time for stop
0.00~5.00[sec]
0.00
○
126
C016
Waiting time for signal
conformation
0.00~5.00[sec] 0.00
○
126
C017 Releasing
frequency
0~99.99/100.0~400.0[Hz]
0.00
○
126
C018
Releasing current
Rated current x (0.0~2.0)[times]
1.0
○
126
C019 BRD
selection
0(INVALID), 1(VAL. Exclude ST),
2(VAL. Include ST)
0
○
128
C020
BRD ON level
330~380/660~760
360
(720)
○
128
C021
BRD using ratio
0.0~100 %
0.0
○
128
C022 PID
selection
0(Disable),
1(Enable), 2(Reverse Enable)
0
○
129
C023 PID-P
gain
0.0~5.0
2.0
○
129
C024 PID-I
gain
0~3600[sec]
1
○
129