4. Parameter Code List
36
4.2.7
Intelligent input terminal setting (I-group)
Code
Function name
Setting range
Initial
data
Change
mode
on run
Page
I001
Intelligent input 1 setting
17
○
85
I002
Intelligent input 2 setting
16
○
85
I003
Intelligent input 3 setting
6
○
85
I004
Intelligent input 4 setting
11
○
85
I005
Intelligent input 5 setting
9
○
85
I006
Intelligent input 6 setting
3
○
85
I007
Intelligent input 7 setting
2
○
85
I008
Intelligent input 8 setting
Intelligent input setting reference
1
○
85
I009
Intelligent input 1 selection
0
○
87
I010
Intelligent input 2 selection
0
○
87
I011
Intelligent input 3 selection
0
○
87
I012
Intelligent input 4 selection
0
○
87
I013
Intelligent input 5 selection
0
○
87
I014
Intelligent input 6 selection
0
○
87
I015
Intelligent input 7 selection
0
○
87
I016
Intelligent input 8 selection
Intelligent input setting
(a/b contact setting)
0 (N.O.), 1(N.C.)
0
○
87
I017
FW input terminal selection
0 (N.O.), 1(N.C.)
0
○
87
I018
O input span calibration
0~9999
Factory
setting
○
104
I019
O input zero calibration
0~9999
Factory
setting
○
104
I020
O start frequency
0~99.99/100.0~400.0[Hz]
0.00
○
104
I021
O end frequency
0~99.99/100.0~400.0[Hz]
0.00
○
104
I022
O start voltage
0~100[%]
0
○
104
I023
O end voltage
0~100[%]
100
○
104
I024
O start selection
0(EXT. FREQ.), 1(ZERO HZ)
1
○
104
I025
OI input span calibration
0~9999
Factory
setting
○
105
I026
OI input zero calibration
0~9999
Factory
setting
○
105
I027
OI start frequency
0~99.99/100.0~400.0[Hz]
0.00
○
105
I028
OI end frequency
0~99.99/100.0~400.0[Hz]
0.00
○
105
I029
OI start voltage
0~100[%]
0
○
105
I030
OI end voltage
0~100[%]
100
○
105
I031
OI start selection
0(EXT. FREQ.), 1(ZERO HZ)
1
○
105
I032
O2 input span calibration
0~9999
Factory
setting
○
106
I033
O2 input zero calibration
0~9999
Factory
setting
○
106
I034
O2 start frequency
0.0~99.9/100~400[Hz]
0.0
○
106
I035
O2 end frequency
0.0~99.9/100~400[Hz]
0.0
○
106
I036
O2 start voltage
-100~100[%]
-100
○
106
I037
O2 end voltage
-100~100[%]
100
○
106
I038
O2 start selection
0(SINGLE), 1(AUX. NO REV), 2(AUX. REV)
0
ⅹ
106
I046
Analog input filter factor
1~30
8
○
107