N700 Operating Instructions and Parts Manual
16. Specification
157
Inverter Model
Common specification for all model
Intelligent output
terminal
Open collect output 4 terminal, relay(c connect) 2 terminal selection :
RUN(Signal during run), FA1(Frequency arrival type 1 signal),
FA2(Frequency arrival type 2 signal), OL(Overload advance notice signal),
OD(Output deviation for PID control), ALM(Alarm signal),
FA3(Arrival signal for only setting frequency), OTQ(Over torque),
IP(Instantaneous stop signal), UV(Under voltage signal),
TRQ(Torque limit), RNT(RUN time over), ONT(ON time over),
THM(Thermal caution), BRK(Brake opening), BER(Brake error),
ZS(Zero speed detect signal), DSE(Speed deviation excessive),
POK(Positioning completion),
FA4(Arrival signal for over setting frequency2),
FA5(Arrival signal for only setting frequency2),
OL2(Overload advance notice signal2),
IPALM(Instantaneous power failure alarm signal),
UVALM(Under voltage alarm signal)
Output
Intelligent monitor
output terminal
Analog voltage output, analog current output, pulse line output
Display monitor
Output frequency, output current, frequency conversion value, trip history,
input output terminal state, input electric power, output voltage, motor
torque
Main function
V/F free setting(7points), Upper/lower frequency limiter, Frequency jump,
curve adjustable speed, manual torque boost level/Braking point, Analog
meter adjustment, Starting frequency, Carrier frequency adjustment,
Electronic thermal, Free setting, External start/end (frequency / rate),
Analog input selection, Trip retry, Reduced voltage start, Overload
restriction, Restarting after an instantaneous power failure, Various kinds
signal output, Initialization value setting, Automatic deceleration at the time
of the power supply block, AVR function, Auto turning(Online/Offline)
Protection function
Over-current, over-voltage, under-voltage, electronic thermal level,
Temperature option error, abnormal trouble, ground fault current on
starting, instantaneous stop, USP error, open-phase error, control resistor
over load, external trip, communication error.
Standard application
Lower voltage provision (Low voltage directive 72/73/EEC),
EMC provision (EMC Directive 2004/108/EC), CE, UL, cUL
Frequency
temperature /
Preservation
temperature /
Humidity
-10 ~ 50
/
℃
-20 ~ 65
/ 20 ~ 90% RH(installed with no dew condensation)
℃
Vibration
5.9m/s
2
(0.6G),
10 ~ 55Hz(5.5~22㎾)
2.94m/s
2
(0.3G),
10 ~ 55Hz(30~132㎾)
Usage
surrounding
Using place
Under 1000m above sea level, indoors (Installed away from corrosive
gasses dust)
Paint color
DIC-582(upper case), DIC-P819(lower case)
Internal option
Feedback unit, Profibus unit
Other
option
Exterior option
Operator with copy function, cable for operator, braking resistor,
regenerative control unit, alternating reactor, D.C. reactor,
EMC Mains filter, higher harmonic control unit, LCR filter, applied control
installation
Operator
OPE-N7 (4line LED)
Table 16- 3 Common specification for 200V/400V class