N700 Operating Instructions and Parts Manual
4. Parameter Code List
34
4.2.6
Operating condition setting(b-group).
Code
Function name
Setting range
Initial
data
Change
mode
on run
Page
b001
Operation direction restrict
0(All Enable), 1(FW Enable), 2(REV Enable)
0
○
69
b003
Reduced voltage start selection
0(start reduced voltage, short time) ~ 6(start
reduced voltage, long time)
0
○
69
b004
Instantaneous power failure/under-
voltage retry time selection
0(Restart until 16th), 1(Restart freely)
0
○
69
b005
Stop key enable
0(valid), 1(invalid)
0
○
70
b006
Stop mode selection
0(Decel. Stop), 1(FRS), 2(DCBR)
0
ⅹ
70
b007 FRS
selection
0(ZERO Hz), 1(Fmat (at FRS function setting)),
2(Speed search (at starting))
0
○
70
b008
AVR selection
0(ALWAYS EN), 1(ALWAYS DIS), 2(Decel. Dis)
0
ⅹ
71
b009
Frequency scaling
conversion factor
0.1~99.9 1.0
○
71
b010 Carrier
frequency
0.5~10.0[kHz]
5.0
ⅹ
71
b011
Cooling fan control
0(ALWAYS EN), 1(OPR. EN)
0
ⅹ
72
b012 Debugger
mode
selection
0~100
0
ⅹ
72
b013
Ground fault
0(invalid), 1(valid)
0
x
72
b014 Initialize
mode
0(TRIP ONLY), 1(DATA ONLY),
2(TRIP+DATA)
0
ⅹ
72
b015
Country code for initialization
0(LOCAL), 1(EC), 2(USA)
0
ⅹ
73
b016 Retry
selection
0(TRIP), 1(ZERO Hz), 2(FREQ MAT),
3(F-D-TRIP)
0
○
73
b017
Allow under-voltage power
failure time
0.3~1.0[sec] 1.0
○
73
b018 Retry
wait
time
0.3~100.0[sec]
1.0
○
73
b019
Instantaneous power failure/
under-voltage trip during stop
0(Invalid), 1(Valid), 2(ST/DEC Dis),
3(Always Invalid: P-N DC)
0
○
73
b020
Frequency setting to match
0~99.99/100.0~400.0[Hz]
0.00
○
74
b021
Non-stop function section
at Instantaneous power failure
0(invalid), 1(valid)
0
ⅹ
77
b022
Starting voltage of non-stop
function at Instantaneous
power failure
0.0~999.9[V] 0.0
ⅹ
77
b023
Non-stop instantaneous power failure
LADSTOP level
0.0~999.9[V] 0.0
ⅹ
77
b024
Non-stop deceleration time at
instantaneous power failure
0.1~99.99/100.0~999.9/1000~3600[sec] 1.0
ⅹ
77
b025
Starting deceleration width at
instantaneous power failure
0.00~10.00[Hz] 0.00
ⅹ
77
b026
Open phase protection
selection
0(Invalid), 1(Valid)
0
○
78
b027
Electronic thermal level
0.0~999.9[A]
Irate
○
78
b227
Electronic thermal level,
2nd motor
0.0~999.9[A] Irate
○
78
b028
Electronic thermal characteristic
selection
0(DECEL TORQ.), 1(CONST TOQR.)
1
○
78
b228
Electronic thermal characteristic
selection, 2nd motor
0(DECEL TORQ.), 1(CONST TOQR.)
1
○
78
b029
Electronic thermal warning level
0~100[%]
80
○
78
b030
Overload restriction selection
0(Disable), 1(ACCEL/CONST), 2(CONST),
3(ACCEL/CST(RE))
1
○
80
b031
Overload restriction level
Inverter rated current*0.5 ~ 2.0[times]
1.5
○
80
b032
Overload restriction limit constant
0.1~30.0[sec]
3.0
○
80
b033
Overload advance notice signal
output mode
0(Accel/Decel/Const), 1(Const)
0
○
80