N700 Operating Instructions and Parts Manual
6. Explanation of F-Group Function
48
6.4
Starting frequency setting (F004)
(1) This frequency is the value the operator must set before the Inverter will give an output.
(2) Mainly use when an operator adjusts the starting torque.
(3) By setting the start frequency higher, direct starting is caused and the starting current
increases.
(4) Therefore an overload is within the restriction range and the inverter has a tendency to trip on
over-current protection
Code
Function name
Initial value
Unit
Setting range
Contents
F004
Starting frequency
setting
0.50 Hz
0.10~10.00 0.10~9.99
: Setting by 0.01Hz
Table 6- 4 Starting frequency setting (F004)
1) Reduced voltage start selection b003=0 2) Reduced voltage start selection b003
≠
0
Fig. 6- 4 Starting frequency setting curve
6.5
Frequency limit (F005/F205 ~ F006/F206)
z
This function can set a upper and lower limit of the output frequency.
z
Even if a frequency command exceeds the upper and lower limit, the inverter will ignore this
value and stop at the values set.
z
Set first upper limit on setting.
z
Be sure that the upper limit (F005)
≥
lower limit (F006).
z
The upper and lower limit will not operate if 0Hz is set.
Code
Function
name
Initial
value
Unit
Setting
range
Contents
F005
Frequency
Upper limit
0.00
Hz
0.00,
F006~F003
0.00 : Frequency limitation setting is
unavailable
0.00~99.99 : Unit 0.01Hz
100.0~400.0: Unit 0.1Hz
F006
Frequency
Lower limit
0.00
Hz
0.00,
F004~F005
0.00 : Frequency limitation setting is
unavailable
0.00~99.99 : Unit 0.01Hz
100.0~400.0: Unit 0.1Hz
F205
Frequency
upper limit,
2nd motor
0.00
Hz
0.00,
F206~F203
0.00 : Frequency limitation setting is
unavailable
0.00~99.99 : Unit 0.01Hz
100.0~400.0: Unit 0.1Hz
F206
Frequency
lower limit,
2nd motor
0.00
Hz
0.00,
F004~F205
0.00 : Frequency limitation setting is
unavailable
0.00~99.99 : Unit 0.01Hz
100.0~400.0: Unit 0.1Hz
Table 6- 5 Frequency limit (F005/F205 ~ F006/F206)