N700 Operating Instructions and Parts Manual
4. Parameter Code List
35
Code
Function name
Setting range
Initial
data
Change
mode
on run
Page
b034 Thermistor
selection
0(Disable), 1(PTC), 2(NTC)
0
○
81
b035
Thermistor error level
0~9999[
Ω
] 3000
○
81
b036 Thermistor
adjustment
0.0~999.9
105.0
○
81
b037
Data command selection
0(OPERATOR), 1(RS485), 2(OPT1), 3(OPT2),
4(RS232)
0
ⅹ
82
b038
Communicating transmission speed
0(2400BPS), 1(4800BPS), 2(9600BPS),
3(19200BPS), 4(38400BPS)
2
ⅹ
82
b039 Communication
code
1~32
1
○
82
b040 Communication
bit
7(BIT),
8(BIT)
8
○
82
b041 Communication
parity
0(NO Parity), 1(Even Parity),
2(Odd Parity)
0
○
82
b042
Communication stop bit
1(1Bit), 2(2itT)
1
○
82
Table 4- 6 Operating curve setting(b-group)