N700 Operating Instructions and Parts Manual
9. Explanation of I-Group Function
104
9.3
Analog order setting
Set output frequency about external outside analog input signal.
9.3.1
O-L terminal setting
(1) External setting output frequency in case input 0~10 V voltage to external analog input
terminal O-L.
Code
Function
Initial
value
Unit
Setting range
Contents
I018
O input span
calibration
Factory
setting
- 0~9999.
Factory
setting
I019
O input zero
calibration
Factory
setting
- 0~9999.
Factory
setting
I020
O Start frequency
0.00
Hz
0.00~400.0
Start frequency setting
I021
O End frequency
0.00
Hz
0.00~400.0
End frequency setting
I022
O Start voltage
0
%
0~100
Starting point for the voltage input 0V
I023
O End voltage
100
%
0~100
Ending point for the voltage input 10V
0
external frequency : 0 ~ I022 output
frequency to I020 output
I024
O Start selection
1
-
1
0Hz : 0 ~ I022 value of output frequency to
0Hz is output
Table 9- 17 O-L terminal setting
Fig. 9- 26 Start frequency setting in O-L terminal setting
(2) When using 5V for O-L terminal, please setting I023 by 50%.
(3) When an initial value 0 ~ the maximum frequency (F003) does not agree with the input
external voltage signal 0~10 V, change correctly I018 and I019.