N700 Operating Instructions and Parts Manual
2. Installation and Wiring
7
(9) Approximate loss for each capacity
At surrounding temperature 40ºC, Air pressure 1.07kg/m³, Air specific heat 0.24kcal/kg·ºC
Inverter
capacity(
㎾
)
5.5 7.5
11
15
18.5
22
30
37
45
55
75
90 110
132
70% of rated
output(W)
242 312 435 575
698 820 1100 1345 1625 1975 2675 3375 3900 4670
100% of rated
output(W)
325 425 600 800
975 1150 1550 1900 2300 2800 3800 4800 5550 6650
100% of rated
output /
efficiency(%)
95.4 96.3 96.1 96.0 96.0 96.4
-
-
-
-
-
-
-
-
Table 2- 1 Approximate loss for each capacity
2.1.2
Blind cover of wiring parts
(1) Cable entry through Rubber Bushings
The wiring should be done after making a cut in the rubber bushings with nippers or
cutters.
If you want to use the conduit, after taking out the rubber bushings, connect the conduit.
Fig. 2- 4 Cable entry through Rubber Bushings
Note)
Except for when connecting conduit, do not remove the rubber bushings.
In the event of the possibility of wiring insulation breakdown, there is the potential of a possible
earth fault.
Wiring cover
Rubber bushings