N700 Operating Instructions and Parts Manual
4. Parameter Code List
28
4.2
Code List
4.2.1 Monitor
mode(d-group)
Code
Function name
Setting range
Initial
Data
Change
mode
on run
Page
d001
Output frequency monitor
0~99.99/100.0~400.0[Hz]
0.00
-
42
d002
Driving direction monitor
F(forward), r(reverse), o(stop)
o
-
42
d003
Output current monitor
0.0~999.9[A]
0.0
-
42
d004
Output voltage monitor
0.0~999.9[V]
0.0
-
42
d005
DC link voltage monitor
0.0~999.9[V]
--
-
42
d006
Motor input power monitor
0.0~999.9[
㎾
]
0.0 - 42
d007
Output torque monitor
-300~300[%]
0
-
43
d008
Number of motor rotation
0~9999[RPM]
0
-
43
d009
PID Feedback monitor
0.00~100.0 (= PID F/B
ⅹ
C026) [%]
0.00 - 43
d010
Intelligent input
terminal monitor
Display the state of the intelligent input
terminals
- - 43
d011
Intelligent output
terminal monitor
Display the state of the intelligent output
terminals
- - 43
d012
Frequency conversion monitor
0.00~99.99/100.0~400.0 (=d001xb009)
0.00
-
44
d013
Accumulated time monitor
during RUN(Hr)
0~9999./1000~6553[Hr] 0
-
44
d014
Accumulated time monitor
during RUN (Min)
0~59[Min] 0
-
44
d015
Power on time monitor(Hr)
0~9999./1000~6553[Hr]
0
-
44
d016
Power on time monitor(Min)
0~59[Min]
0
-
44
Table 4- 1 Basic Display
4.2.2
Trip & Warning monitor mode(d-group)
Code
Function name
Setting range
Initial
Data
Change
mode
on run
Page
d017
IGBT temperature monitor 0~9999[
℃
]
--
- 44
d018
Trip counter
Display the number of inverter trips.
0
- 44
d019
Trip monitor 1
--
- 44
d020
Trip monitor 2
--
- 44
d021
Trip monitor 3
--
- 44
d022
Trip monitor 4
--
- 44
d023
Trip monitor 5
--
- 44
d024
Trip monitor 6
Display the details for the last six protective trips.
Trip code, output frequency[Hz], output current[A], the direct
voltage (between P and N) on tripping[V].
--
- 44
Table 4- 2 Trip & Warning monitor