N700 Operating Instructions and Parts Manual
9. Explanation of I-Group Function
85
(4) In case of using external source : (Please take off the short bar of control terminal.)
Fig. 9- 4 Intelligent input terminal connection (Sink Type:P24-PLC)
Fig. 9- 5 Intelligent input terminal connection (Source Type:PLC-CM1)
9.1.3
Input terminal function selection (I001~I008)
(1) It is possible to use functions by assigning those functions to the intelligent input terminals 1-
8(I001-I008).
(2) The intelligent input terminals(1-8) can be set as a NO or a NC contact separately.
Two or more intelligent input terminals can't be assigned to be the same function.
(3) If a function tries to be assigned to an intelligent input terminal where another terminal already
has the function, the new terminal will automatically be restored back to the previous setting.
code
Function
name
Code
value
Contents
Item
1
REV
Reverse driving
Operation command
2
CF1
Multi-speed 1 (binary operation)
3
CF2
Multi-speed 2 (binary operation)
4
CF3
Multi-speed 3 (binary operation)
5
CF4
Multi-speed 4 (binary operation)
Multi-speed operation function
6 JOG
Jogging
Jogging
operation
7
DB
External DC braking
DC braking(external DC braking)
8
SET2 2nd Set of Motor Data
2nd Set of Motor Data
9 2CH
Two-stage
adjustable-speed
10 3CH
Three-stage
adjustable-speed
Two/Three-stage adjustable-
speed function
11
FRS
Free run stop
Free run stop
I001
~
I008
Intelligent
input
terminals
1~8
12
EXT
External trip
External trip