N700 Operating Instructions and Parts Manual
9. Explanation of I-Group Function
91
(4) Jogging operation selection
Note)
When using the jogging function, turn FW terminal or RV terminal ON after the JG
terminal is turned ON. (It is the same when the operation command point is from the
operator.)
Fig. 9- 12 Jogging operation selection (When setting of A039 is 03, 04 or 05 and FW
terminal is turned ON beforehand, the inverter operates jogging.)
Note)
In the case that the setting of A074 is 02, data setting of DB is necessary.
(5) Set an intelligent input terminal(I001~I008) to 06 (JG). (Initial value : I003 =6)
Fig. 9- 13 Jogging operation selection in the intelligent input terminal
9.2.4
Direct current braking (DB : External DC Braking)
(1) Please set 7 (DB) to an Intelligent input terminal.
(2) DC braking is then switched by ON/OFF of DB terminal irrespective of DC braking selection
A081.
(3) Set DC braking force with A084.
(4) If DC braking time A083 is set, the Inverter output is cut off for this time period, the motor will
be free-running. After the setting time passes, DC braking is started.
(5) Please set DC braking time A085 or DC braking time by DB terminal paying attention to the
heat of the motor.
Note) Please refer to 7.10 (DC braking setting) for details.
9.2.5
Second control function (SET2)
(1) Please set 8 (SET 2) to Intelligent input terminals 1~8 (function code I001~I008).
(2) By assigning 08 (SET 2) to an intelligent input terminal and turning SET2 terminal ON/OFF
you can switch between two different inverter set-ups.
The functions which can change with SET terminal are as following.