N700 Operating Instructions and Parts Manual
6. Explanation of F-Group Function
51
6.9
RUN command source setting (F011)
(1) Select the control of RUN/STOP commands.
(2) Operate start/stop with RUN key/STOP key on the digital operator when operating from digital
operator.
Code Function name
Initial
value
Unit
Setting
range
Contents
1
Ter : Start/stop with control terminals
(Terminals: FW, REV)
2
OPE : Start/stop with digital operator (F001)
3
COM : Start/stop with RS485 terminals for
communication
4
OPT1 : Setting frequency with option board 1.
F011
RUN
command
source setting
2 -
5
OPT2 : Setting frequency with option board 2.
Table 6- 9 RUN command source setting (F011)
(3) Operation command from the control terminals (Terminal) start/stop by ON/OFF of control
terminals.
(4) Put 01(REV) to an intelligent input terminal. When using the FW terminal, it is possible the
change the contact from NO to NC by setting a or b (respectively) in I009~I017.
* Forward : FW-CM1 terminal
* Reverse : REV-CM1 terminal
Note)
Refer to the input terminal function setting reference.
(5) When forward command and reverse command entered simultaneously, operation command
becomes stop command.
Ex. ) The setting method of operation command on intelligent input terminals
F011=1(TER), I008=1(REV) Setting
Inverter control terminal
block
The composition of
external contacts