GE Multilin
G60 Generator Protection System
B-15
APPENDIX B
B.4 MEMORY MAPPING
B
1C16
Source 1 Phase C Apparent Power
-1000000000000 to
1000000000000
VA
0.001
F060
0
1C18
Source 1 Three Phase Power Factor
-0.999 to 1
---
0.001
F013
0
1C19
Source 1 Phase A Power Factor
-0.999 to 1
---
0.001
F013
0
1C1A
Source 1 Phase B Power Factor
-0.999 to 1
---
0.001
F013
0
1C1B
Source 1 Phase C Power Factor
-0.999 to 1
---
0.001
F013
0
1C1C
Reserved (4 items)
---
---
---
F001
0
1C20
...Repeated for Source 2
1C40
...Repeated for Source 3
1C60
...Repeated for Source 4
Source Energy Metering (Read Only Non-Volatile) (4 modules)
1D00
Source 1 Positive Watthour
0 to 1000000000000
Wh
0.001
F060
0
1D02
Source 1 Negative Watthour
0 to 1000000000000
Wh
0.001
F060
0
1D04
Source 1 Positive Varhour
0 to 1000000000000
varh
0.001
F060
0
1D06
Source 1 Negative Varhour
0 to 1000000000000
varh
0.001
F060
0
1D08
Reserved (8 items)
---
---
---
F001
0
1D10
...Repeated for Source 2
1D20
...Repeated for Source 3
1D30
...Repeated for Source 4
Energy Commands (Read/Write Command)
1D60
Energy Clear Command
0 to 1
---
1
F126
0 (No)
Source Frequency (Read Only) (4 modules)
1D80
Frequency for Source 1
2 to 90
Hz
0.001
F003
0
1D82
Frequency for Source 2
2 to 90
Hz
0.001
F003
0
1D84
Frequency for Source 3
2 to 90
Hz
0.001
F003
0
1D86
Frequency for Source 4
2 to 90
Hz
0.001
F003
0
Source Voltage THD and Harmonics (Read Only) (4 modules)
1F80
Source 1 Va THD
0 to 99.9
---
0.1
F001
0
1F81
Source 1 Va Harmonics - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
1F99
Source 1 Vb THD
0 to 99.9
---
0.1
F001
0
1F9A
Source 1 Vb Harmonics - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
1FB2
Source 1 Vc THD
0 to 99.9
---
0.1
F001
0
1FB3
Source 1 Vc Harmonics - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
1FCB
...Repeated for Source 2
2016
...Repeated for Source 3
2061
...Repeated for Source 4
Breaker Flashover (Read/Write Setting) (2 modules)
2196
Breaker Flashover 1 Function
0 to 1
---
1
F102
0 (Disabled)
2197
Breaker Flashover 1 Side 1 Source
0 to 5
---
1
F167
0 (SRC 1)
2198
Breaker Flashover 1 Side 2 Source
0 to 6
---
1
F211
0 (None)
2199
Breaker Flashover 1 Status Closed A
0 to 4294967295
---
1
F300
0
219B
Breaker Flashover 1 Status Closed B
0 to 4294967295
---
1
F300
0
219D
Breaker Flashover 1 Status Closed C
0 to 4294967295
---
1
F300
0
219F
Breaker Flashover 1 Voltage Pickup Level
0 to 1.5
pu
0.001
F001
850
21A0
Breaker Flashover 1 Voltage Difference Pickup Level
0 to 100000
V
1
F060
1000
21A2
Breaker Flashover 1 Current Pickup Level
0 to 1.5
pu
0.001
F001
600
21A3
Breaker Flashover 1 Pickup Delay
0 to 65.535
s
0.001
F001
100
21A4
Breaker Flashover 1 Supervision Phase A
0 to 4294967295
---
1
F300
0
21A6
Breaker Flashover 1 Supervision Phase B
0 to 4294967295
---
1
F300
0
21A8
Breaker Flashover 1 Supervision Phase C
0 to 4294967295
---
1
F300
0
21AA
Breaker Flashover 1 Block
0 to 4294967295
---
1
F300
0
21AC
Breaker Flashover 1 Events
0 to 1
---
1
F102
0 (Disabled)
21AD
Breaker Flashover 1 Target
0 to 2
---
1
F109
0 (Self-Reset)
21AE
Reserved (4 items)
---
---
---
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 7 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...