5-58
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The settings menu for the fast EGD exchange is shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
EGD PROTOCOL
FAST PROD EXCH 1 CONFIGURATION
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The G60 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the slow EGD exchanges is shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
EGD PROTOCOL
SLOW PROD EXCH 1(2) CONFIGURATION
Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are described below:
•
EXCH 1 DESTINATION
: This setting specifies the destination IP address of the produced EGD exchange. This is usu-
ally unicast or broadcast.
•
EXCH 1 DATA RATE
: This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms,
the exchange data will be updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data will be
updated and sent once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a
setting range of 500 to 1000 ms.
FAST PROD EXCH 1
CONFIGURATION
EXCH 1 FUNCTION:
Disable
Range: Disable, Enable
MESSAGE
EXCH 1 DESTINATION:
0.0.0.0
Range: standard IP address
MESSAGE
EXCH 1 DATA RATE:
1000 ms
Range: 50 to 1000 ms in steps of 1
MESSAGE
EXCH 1 DATA ITEM 1:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
MESSAGE
EXCH 1 DATA ITEM 2:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
MESSAGE
EXCH 1 DATA ITEM 3:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
↓
MESSAGE
EXCH 1 DATA ITEM 20:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
SLOW PROD EXCH 1
CONFIGURATION
EXCH 1 FUNCTION:
Disable
Range: Disable, Enable
MESSAGE
EXCH 1 DESTINATION:
0.0.0.0
Range: standard IP address
MESSAGE
EXCH 1 DATA RATE:
1000 ms
Range: 500 to 1000 ms in steps of 1
MESSAGE
EXCH 1 DATA ITEM 1:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
MESSAGE
EXCH 1 DATA ITEM 2:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
MESSAGE
EXCH 1 DATA ITEM 3:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
↓
MESSAGE
EXCH 1 DATA ITEM 50:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...