GE Multilin
G60 Generator Protection System
5-135
5 SETTINGS
5.4 SYSTEM SETUP
5
reflects the state of the SvEna control where “1”= Enabled and “0”=Disabled. The logic for setting the SvEna control bit
is shown in the following figure.
Figure 5–52: LOGIC FOR SETTING SVENA CONTROL BIT
•
MSVCB 1 Client CONTRL:
This setting determines if a client can write to the reserve bit. When the assigned Flex-
Logic operand is a logic 1 state, remote clients can write to both the reserve bit and the SvEna bit. When the FlexLogic
operand is a logic 0 state, the remote client writes to the reserve bit, the SvEna is rejected by the UR, and a negative
response with the appropriate Service Error is returned to the client.
•
MSVCB 1 SVENA Default:
This setting sets the default state of the stream (On or Off) on power-up or restart.
•
MSVCB 1 CONFREV:
The relay increments the Configuration revision every time the configuration is changed. This
setting allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
•
MSVCB 1 PRIORITY:
A value from 0 through 7: The default value is 4.
•
MSVCB 1 IP Class:
The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The
default value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing, when sup-
ported in the routers.
•
MSVCB 1 VID:
A range of values limited from 0 to 4095.
•
MSVCB 1 APPID:
This setting allows the selection of a specific application ID for each sending device.
•
MSVCB 1 DEST IP Address:
This is the destination multicast address IP address that is entered in Standard IPV4
address format. The valid range for IPv4 is from 224.0.0.0 to 239.255.255.255, but the UR does not test the address
entered.
•
MSVCB 1 Security:
This setting selects the level of security and authentication used, as outlined in the following table,
and is in the form of an enumeration as per standard. The range is 0 to 2.
Shaded settings in the table are not supported in firmware 7.0.
ENUMERATION
AUTHENTICATION
ENCRYPTION
0
no
no
1
yes
no
2
yes
yes
Toggle Function
AND
AND
Positive
One-Shot
SvEna
Status
Pushbutton/
FlexOperand
(Momentary)
Write “0”
to SvEna
Write “1”
to SvEna
859739A1.cdr
NOTE
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...