B-48
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
8469
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
846B
EGD Slow Producer Exchange 1 Data Rate
500 to 1000
ms
50
F001
1000
846C
EGD Slow Producer Exchange 1 Data Item 1 (50 items)
0 to 65535
---
1
F001
0
849E
Reserved (50 items)
---
---
---
F001
0
84D0
...Repeated for EGD Exchange 2
Breaker Failure (Read/Write Grouped Setting) (4 modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 4294967295
---
1
F300
0
8607
Breaker Failure 1 Block
0 to 4294967295
---
1
F300
0
8609
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860A
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860B
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
8610
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 4294967295
---
1
F300
0
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 4294967295
---
1
F300
0
8615
Breaker Failure 1 Breaker Test On
0 to 4294967295
---
1
F300
0
8617
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8619
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861A
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861B
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
861C
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
861D
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
861E
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861F
Breaker Failure 1 Phase A Initiate
0 to 4294967295
---
1
F300
0
8621
Breaker Failure 1 Phase B Initiate
0 to 4294967295
---
1
F300
0
8623
Breaker Failure 1 Phase C Initiate
0 to 4294967295
---
1
F300
0
8625
Breaker Failure 1 Breaker Status 1 Phase B
0 to 4294967295
---
1
F300
0
8627
Breaker Failure 1 Breaker Status 1 Phase C
0 to 4294967295
---
1
F300
0
8629
Breaker Failure 1 Breaker Status 2 Phase B
0 to 4294967295
---
1
F300
0
862B
Breaker Failure 1 Breaker Status 2 Phase C
0 to 4294967295
---
1
F300
0
862D
...Repeated for Breaker Failure 2
865A
...Repeated for Breaker Failure 3
8687
...Repeated for Breaker Failure 4
Remote RTD Inputs (Read Only Actual Values) (12 modules)
87C0
Remote RTD 1 Value
0 to 200
°C
1
F002
0
87C1
Remote RTD 2 Value
0 to 200
°C
1
F002
0
87C2
Remote RTD 3 Value
0 to 200
°C
1
F002
0
87C3
Remote RTD 4 Value
0 to 200
°C
1
F002
0
87C4
Remote RTD 5 Value
0 to 200
°C
1
F002
0
87C5
Remote RTD 6 Value
0 to 200
°C
1
F002
0
87C6
Remote RTD 7 Value
0 to 200
°C
1
F002
0
87C7
Remote RTD 8 Value
0 to 200
°C
1
F002
0
87C8
Remote RTD 9 Value
0 to 200
°C
1
F002
0
87C9
Remote RTD 10 Value
0 to 200
°C
1
F002
0
87CA
Remote RTD 11 Value
0 to 200
°C
1
F002
0
Table B–10: MODBUS MEMORY MAP (Sheet 40 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...