GE Multilin
G60 Generator Protection System
B-79
APPENDIX B
B.4 MEMORY MAPPING
B
F120
ENUMERATION: DISTANCE SHAPE
0 = Mho, 1 = Quad
Fixed at Mho in G60.
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
F124
ENUMERATION: LIST OF ELEMENTS
Bitmask
Element
0
Phase Instantaneous Overcurrent 1
1
Phase Instantaneous Overcurrent 2
16
Phase Time Overcurrent 1
24
Phase Directional Overcurrent 1
32
Neutral Instantaneous Overcurrent 1
48
Neutral Time Overcurrent 1
56
Neutral Directional Overcurrent 1
57
Neutral Directional Overcurrent 2
60
Negative Sequence Directional Overcurrent 1
61
Negative Sequence Directional Overcurrent 2
64
Ground Instantaneous Overcurrent 1
80
Ground Time Overcurrent 1
86
Restricted Ground Fault 1
87
Restricted Ground Fault 2
88
Restricted Ground Fault 3
89
Restricted Ground Fault 4
90
Restricted Ground Fault 5
91
Restricted Ground Fault 6
101
Change Phase Rotation
120
Negative Sequence Overvoltage 1
121
Negative Sequence Overvoltage 2
122
Negative Sequence Overvoltage 3
125
Generator Unbalance
140
Auxiliary Undervoltage 1
141
Auxiliary Undervoltage 2
142
Auxiliary Undervoltage 3
144
Phase Undervoltage 1
145
Phase Undervoltage 2
146
Phase Undervoltage 3
148
Auxiliary Overvoltage 1
149
Auxiliary Overvoltage 2
150
Auxiliary Overvoltage 3
152
Phase Overvoltage 1
156
Neutral Overvoltage 1
157
Neutral Overvoltage 2
158
Neutral Overvoltage 3
160
Phase Distance Zone 1
161
Phase Distance Zone 2
162
Phase Distance Zone 3
190
Power Swing Detect
210
Volt per Hertz 1
211
Volt per Hertz 2
214
Sensitive Directional Power 1
215
Sensitive Directional Power 2
221
100% Stator Ground
222
Split Phase Protection
224
SRC1 VT Fuse Failure
225
SRC2 VT Fuse Failure
226
SRC3 VT Fuse Failure
227
SRC4 VT Fuse Failure
232
SRC1 50DD (Disturbance Detection)
233
SRC2 50DD (Disturbance Detection)
234
SRC3 50DD (Disturbance Detection)
235
SRC4 50DD (Disturbance Detection)
265
Stator Differential
272
CT Fail1
273
CT Fail 2
274
CT Fail 3
275
CT Fail 4
276
CT Fail 5
277
CT Fail 6
280
Breaker Failure 1
281
Breaker Failure 2
282
Breaker Failure 3
283
Breaker Failure 4
294
Breaker 1 Flashover
295
Breaker 2 Flashover
296
Accidental Energization
300
Loss Of Excitation
311
Phasor measurement unit one-shot
312
Synchrocheck 1
313
Synchrocheck 2
314
Synchrocheck 3
315
Synchrocheck 4
330
Third harmonic neutral undervoltage
336
Setting Group
337
Reset
344
Overfrequency 1
345
Overfrequency 2
346
Overfrequency 3
347
Overfrequency 4
352
Underfrequency 1
353
Underfrequency 2
354
Underfrequency 3
355
Underfrequency 4
356
Underfrequency 5
357
Underfrequency 6
Bitmask
Element
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...