CYBERSENTRY SETTINGS THROUGH THE FRONT PANEL
PATH: SETTINGS
PRODUCT SETUP
SECURITY
Login: This setting is applicable for
Device Authentication
only. This setting allows a user to login with a specific role, see
descriptions below. For the Supervisor role, the “Supervisor Role” setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. Passwords must obey the
requirements specified the Password Requirements section in chapter 8.The UR device supports five roles. All roles have
their corresponding passwords. The Observer role is the only role that does not require a password.
The roles are defined as follows:
•
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
•
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
•
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
•
Supervisor: This is only an approving role. This role’s authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
SETTING NAME
DESCRIPTION / DETAILS
MIN
MAX
DEFAULT UNITS
MINIMUM
PERMISSIONS
Failed
Authentications
A threshold number indicating when an alarm is
set off to indicate too many failed authentication
attempts
0
(disabled)
99
3
-
Administrator
Firmware lock
A Boolean value indicating if the device can
receive a firmware upgrade. If Yes and a
firmware upgrade attempt is made, the device
alarm activates. If No the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
No
Yes
Yes
-
Administrator
Settings lock
A Boolean value indicating if the device can
accept any settings changes. If Yes and a
settings change attempt is made, the device
alarm activates. If No, the device alarm does not
activate.
No
Yes
Yes
-
Supervisor
(Administrator if
Supervisor has
been disabled)
SECURITY
LOGIN:
None
Range: Administrator, Engineer, Supervisor,
Operator, Factory (for factory use only), None
MESSAGE
CHANGE LOCAL
PASSWORDS
MESSAGE
SESSION
SETTINGS
MESSAGE
RESTORE DEFAULTS
MESSAGE
SUPERVISORY
MESSAGE
SYSLOG IP ADDRESS:
0.0.0.0
Range: 0.0.0.0, 255.255.255.255
MESSAGE
SYSLOG PORT NUMBER:
514
Range: 1 to 65535
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...