GE Multilin
G60 Generator Protection System
5-31
5 SETTINGS
5.2 PRODUCT SETUP
5
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols.
The next section explains PRP.
PRT1 (2 OR 3) IP ADDRESS
: This setting sets the ports IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2
REDUNDANCY
is set to None.
PRT1 (2 OR 3) SUBNET MASK
: This setting sets the ports IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2
REDUNDANCY
is set to None.
PRT1 (2 OR 3) GOOSE ENABLED
: This setting enables/disables Goose on the respective port. By default Goose is enabled.
PRT2 REDUNDANCY
determines if ports 2 and 3 operate in redundant or independent mode. If a license for PRP was pur-
chased, the options are None, Failover, and PRP. If a license for PRP was not purchased, the available options are None
and Failover. In non-redundant mode (
REDUNDANCY
set to None), ports 2 and 3 operate independently with their own MAC,
IP, and mask addresses. If
REDUNDANCY
is set to Failover, the operation of ports 2 and 3 is as follows:
•
Ports 2 and 3 use the port 2 MAC address, IP address, and mask
•
The configuration fields for IP address and mask on port 3 are hidden
•
Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the Mul-
tilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect, acting as
a redundant or backup link to the network for port 2. Once Port 2 detects that the link between port 2 and the switch is
good, communications automatically switch back to port 2 and port 3 goes back into standby mode.
If
REDUNDANCY
is set to PRP, the operation of ports 2 and 3 is as follows:
•
Ports 2 and 3 use the port 2 MAC address, IP address, and mask
•
The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
•
Port 2
MCST ADDRESS
field is visible
•
The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still synchro-
nizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case for PRP
networks, the port with the better connectivity is used.
The two ports must be connected to completely independent LANS with no single point of failure, such as common
power supplies that feed switches on both LANS.
For this setting change to take effect, restart the unit.
PRT2 PRP MCST ADDR
: This setting allows the user to change the multicast address used by the PRP supervision frames.
This setting is available if
REDUNDANCY
is set to PRP. All devices in the same PRP network need to have the same multi-
cast address. Choose an address that does not conflict with another multicast protocol.
e) FAR-END FAULT INDICATION (FEFI)
Since 100BASE-FX does not support Auto-Negotiation, a Far-End Fault Indication (FEFI) feature is included in UR 7 that
allows for detection of link failures.
The purpose of the Far-End Fault feature is to allow the stations on both ends of a pair of fibers to be informed when there
is a problem with one of the fibers. Without the Far-End Fault feature, it is impossible for a fiber interface to detect a prob-
lem that affects only its transmit fiber.
When the Far-End Fault feature is supported, a loss of receive signal (link) causes the transmitter to generate a Far-End
Fault pattern in order to inform the device at the far end of the fiber pair that a fault has occurred.
NETWORK PORT 3
PRT3 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT3 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NOTE
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...