GE Multilin
G60 Generator Protection System
C-19
APPENDIX C
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
C
•
Header.
•
Substation.
•
Communication.
•
IED section (one or more).
•
DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
Figure C–6: SCD FILE STRUCTURE, SCL (ROOT) NODE
Like ICD files, the
Header
node identifies the SCD file and its version, and specifies options for the mapping of names to
signals.
The
Substation
node describes the substation parameters:
Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE
842791A1.CDR
SCL
Header (id, version, revision, toolID, nameStructure)
IED Section (IED 2)
Communication
IED Section (IED 1)
Substation
Other IED Sections
DataTypeTemplates
842792A1.CDR
Substation
EquipmentContainer
VoltageLevel
Function
PowerSystemResource
Power Transformer
GeneralEquipment
EquipmentContainer
Bay
Voltage
PowerSystemResource
SubFunction
GeneralEquipment
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...