GE Multilin
G60 Generator Protection System
5-159
5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6GROUPED ELEMENTS
5.6.1 OVERVIEW
Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the
SETTING GROUPS
menu (see the
Control elements
section later in this chapter). See also the
Introduction to elements
section at the beginning of this chap-
ter.
5.6.2 SETTING GROUP
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see the
Control elements
section for additional details).
SETTING GROUP 1
DISTANCE
MESSAGE
POWER SWING
DETECT
MESSAGE
STATOR
DIFFERENTIAL
MESSAGE
PHASE CURRENT
MESSAGE
NEUTRAL CURRENT
MESSAGE
GROUND CURRENT
MESSAGE
NEGATIVE SEQUENCE
CURRENT
MESSAGE
GENERATOR
UNBALANCE
MESSAGE
SPLIT PHASE
MESSAGE
BREAKER FAILURE
MESSAGE
VOLTAGE ELEMENTS
MESSAGE
LOSS OF
EXCITATION
MESSAGE
ACCIDENTAL
ENERGIZATION
MESSAGE
POWER
MESSAGE
STATOR
GROUND
MESSAGE
FIELD
GROUND
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...