3-56
G60 Generator Protection System
GE Multilin
3.4 FIELD AND STATOR GROUND MODULES
3 HARDWARE
3
Figure 3–62: REAR VIEW OF GPM-F-HM MODULE SHOWING TERMINAL BLOCKS
The following tables outline the pin assignments.
Three contact inputs are provided. Upon closure of any one of the contact inputs, low frequency injection stops.
There are three connectors on the field ground protection high-voltage resistor box, as shown in the following figure.
Table 3–8: GPM-F-HM PIN ASSIGNMENTS FOR CONNECTOR A
PIN
LABEL
DEFINITION
1
L(+)
AC-L (DC+)
2
N(–)
AC-N (DC–)
3
GND
Ground
Table 3–9: GPM-F-HM PIN ASSIGNMENTS FOR CONNECTOR B
PIN
LABEL
DEFINITION
1
CH1(+)
RS485 channel 1 positive
2
CH1(–)
RS485 channel 1 negative
3
COM
RS485 common
4
CH2(+)
RS485 channel 2 positive
5
CH2(–)
RS485 channel 2 negative
6
IN3
Contact input 3
7
IN2
Contact input 2
8
IN1
Contact input 1
9
COM
Contact input common
10
NC
Relay NC (normally closed)
11
COM
Relay common
12
NO
Relay NO (normally open)
Table 3–10: GPM-F-HM PIN ASSIGNMENTS FOR CONNECTOR C
PIN
LABEL
DEFINITION
1
FGND
Field ground
2
F1
Injection to excitation positive
3
F(–)
Injection to excitation negative / excitation negative
4
F(+)
Excitation positive
&RQQHFWRU$
&RQQHFWRU%
&RQQHFWRU&
$&'5
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...