B-44
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
785A
PMU 1 Voltage Trigger High Voltage
0.75 to 1.75
pu
0.001
F001
1200
785B
PMU 1 Voltage Trigger Pickup Time
0 to 600
s
0.01
F001
10
785C
PMU 1 Voltage Trigger Dropout Time
0 to 600
s
0.01
F001
100
785D
PMU 1 Voltage Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
7863
PMU 1 Voltage Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
7864
PMU 1 Voltage Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit One-shot Command (Read/Write Setting)
788C
PMU One-shot Function
0 to 1
---
1
F102
0 (Disabled)
788D
PMU One-shot Sequence Number
0 to 99
---
1
F001
1
788E
PMU One-shot Time
0 to 235959
---
1
F050
0
Phasor Measurement Unit Test Values (Read/Write Setting)
7890
PMU 1 Test Function
0 to 1
---
1
F102
0 (Disabled)
7891
PMU 1 Phase A Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
7893
PMU 1 Phase A Voltage Test Angle
-180 to 180
°
0.05
F002
0
7894
PMU 1 Phase B Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
7896
PMU 1 Phase B Voltage Test Angle
-180 to 180
°
0.05
F002
-12000
7897
PMU 1 Phase C Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
7899
PMU 1 Phase C Voltage Test Angle
-180 to 180
°
0.05
F002
12000
789A
PMU 1 Auxiliary Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
789C
PMU 1 Auxiliary Voltage Test Angle
-180 to 180
°
0.05
F002
0
789D
PMU 1 Phase A Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
789F
PMU 1 Phase A Current Test Angle
-180 to 180
°
0.05
F002
-1000
78A0
PMU 1 Phase B Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
78A2
PMU 1 Phase B Current Test Angle
-180 to 180
°
0.05
F002
-13000
78A3
PMU 1 Phase C Current Test Magnitude
0 to 9.999
kA
0.001
F003
1000
78A5
PMU 1 Phase C Current Test Angle
-180 to 180
°
0.05
F002
11000
78A6
PMU 1 Ground Current Test Magnitude
0 to 9.999
kA
0.001
F004
0
78A8
PMU 1 Ground Current Test Angle
-180 to 180
°
0.05
F002
0
78A9
PMU 1 Test Frequency
20 to 70
Hz
0.001
F003
60000
78AB
PMU 1 Test df/dt
-10 to 10
Hz/s
0.01
F002
0
Phasor Measurement Unit Recording Values (Read Only)
7900
PMU 1 Available Records
0 to 65535
---
1
F001
0
7901
PMU 1 Second Per Record
0 to 6553.5
---
0.1
F003
0
7903
PMU 1 Last Cleared Date
0 to 400000000
---
1
F050
0
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7914
PMU Network Reporting Function
0 to 1
---
1
F102
0 (Disabled)
7915
PMU Network Reporting ID Code
1 to 65534
---
1
F001
1
7916
PMU TCP Port Number
1 to 65535
---
1
F001
4712
7917
PMU UDP Port Number 1
1 to 65535
---
1
F001
4713
7918
PMU UDP Port Number 2
1 to 65535
---
1
F001
4714
Phasor Measurement Unit Calibration (Read/Write Setting)
7919
PMU 1 Va Calibration Angle
-5 to 5
°
0.05
F002
0
791A
PMU 1 Va Calibration Magnitude
95 to 105
%
0.1
F002
1000
791B
PMU 1 Vb Calibration Angle
-5 to 5
°
0.05
F002
0
791C
PMU 1 Vb Calibration Magnitude
95 to 105
%
0.1
F002
1000
791D
PMU 1 Vc Calibration Angle
-5 to 5
°
0.05
F002
0
791E
PMU 1 Vc Calibration Magnitude
95 to 105
%
0.1
F002
1000
791F
PMU 1 Vx Calibration Angle
-5 to 5
°
0.05
F002
0
7920
PMU 1 Vx Calibration Magnitude
95 to 105
%
0.1
F002
1000
7921
PMU 1 Ia Calibration Angle
-5 to 5
°
0.05
F002
0
7922
PMU 1 Ia Calibration Magnitude
95 to 105
%
0.1
F002
1000
7923
PMU 1 Ib Calibration Angle
-5 to 5
°
0.05
F002
0
7924
PMU 1 Ib Calibration Magnitude
95 to 105
%
0.1
F002
1000
7925
PMU 1 Ic Calibration Angle
-5 to 5
°
0.05
F002
0
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...