5-34
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
•
The route destination and mask must match. This can be verified by checking that
RtDestination and RtMask = RtDestination
Example of good configuration: RtDestination = 10.1.1.0; Rt Mask = 255.255.255.0
Example of bad configuration: RtDestination = 10.1.1.1; Rt Mask = 255.255.255.0
The following rules must be observed when you configure static routes:
•
The route destination must not be a connected network
•
The route gateway must be on a connected network. This rule applies to the gateway address of the default route as
well. This can be verified by checking that:
(RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) ==
(Prt3IP & Prt3Mask)
where
& is the bitwise-AND operator
== is the equality operator
|| is the logical OR operator
ROUTING BEHAVIOR COMPARED TO PREVIOUS RELEASES
Prior to release 7.10, the UR did not have an explicit manner of configuring routes. The only available route was the default
route configured as part of the network settings (port gateway IP address). This limited the ability to route to specific desti-
nations, particularly if these destinations were reachable through a different interface than the one on which the default
gateway was.
Starting with UR 7.10, up to six static network routes can be configured in addition to a default route. The default route con-
figuration was also moved from the network settings into the routing section.
The figure shows an example of topology that benefits from the addition of static routes.
Figure 5–8: USING STATIC ROUTES
In the figure, the UR connects through the following two Ethernet ports:
•
Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router 1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
•
Port 2 (IP address 10.1.2.2) connects the UR to LAN 10.1.2.0/24 and to the EnerVista software through Router 2.
Router 2 has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
The configuration before release 7.10 was as follows:
•
PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT1 GWY IP ADDRESS = 10.1.1.1
EnerVista Software
ML3000
Public network
UR
P1
IP1/
MAC1
P2
IP2/
MAC2
ML3000
10.1.1.0/24
10.1.2.0/24
P3
IP3/
MAC3
Router2
Router1
10.1.3.0/24
.1
.1
.2
.2
859714A1.vsd
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...