B-36
G60 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5C04
Neutral Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5C05
Neutral Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5C07
Neutral Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5C08
Neutral Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5C09
Reserved (8 items)
0 to 1
---
1
F001
0
Ground Time Overcurrent (Read/Write Grouped Setting) (1 module)
5D00
Ground Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5D01
Ground Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5D02
Ground Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5D03
Ground Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5D04
Ground Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5D05
Ground Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5D06
Ground Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5D07
Ground Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5D09
Ground Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5D0A
Ground Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5D0B
Reserved (6 items)
0 to 1
---
1
F001
0
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (1 module)
5DA0
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5DA2
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5DA3
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5DA5
Ground Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5DA7
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5DA8
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5DA9
Reserved (8 items)
0 to 1
---
1
F001
0
CT Fail (Read/Write Setting) (6 modules)
5E6C
CT Fail 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E6D
CT Fail 1 Block
0 to 4294967295
---
1
F300
0
5E6F
CT Fail 1 Current Source 1
0 to 5
---
1
F167
0 (SRC 1)
5E70
CT Fail 1 Current Pickup 1
0 to 2
pu
0.1
F001
2
5E71
CT Fail 1 Current Source 2
0 to 5
---
1
F167
1 (SRC 2)
5E72
CT Fail 1 Current Pickup 2
0 to 2
pu
0.1
F001
2
5E73
CT Fail 1 Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
5E74
CT Fail 1 Voltage Pickup
0 to 2
pu
0.01
F001
20
5E75
CT Fail 1 Pickup Delay
0 to 65.535
s
0.001
F001
1000
5E76
CT Fail 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5E77
CT Fail 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E78
...Repeated for CT Fail 2
5E84
...Repeated for CT Fail 3
5E90
...Repeated for CT Fail 4
5E9C
...Repeated for CT Fail 5
5EA8
...Repeated for CT Fail 6
Frequency Out-Of-Band Accumulation (Read/Write Setting)
5F40
Frequency Out-Of-Band Accumulation Block
0 to 4294967295
---
1
F300
0
5F42
Frequency Out-Of-Band Accumulation Events Enable
0 to 1
---
1
F102
0 (Disabled)
5F43
Frequency Out-Of-Band Accumulator Function Enable
Array (7 items)
0 to 1
---
1
F102
0 (Disabled)
5F4A
Frequency Out-Of-Band Accumulator Lower Frequency
Array (7 items)
20 to 70
Hz
0.01
F001
6000
5F51
Frequency Out-Of-Band Accumulator Min Value V A
0.1 to 1.25
pu
0.01
F001
10
5F52
Frequency Out-Of-Band Accumulator Source
0 to 5
---
1
F167
0 (SRC 1)
5F53
Frequency Out-Of-Band Accumulator Target Messages
Enable
0 to 2
---
1
F109
0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...