5-24
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Activity Value
— 16 bit unsigned
5.2.2 DISPLAY PROPERTIES
PATH: SETTINGS
PRODUCT SETUP
DISPLAY PROPERTIES
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
•
LANGUAGE
: This setting selects the language used to display settings, actual values, and targets. The setting dis-
plays when a language other than English was purchased, and the range depends on the order code of the relay.
•
FLASH MESSAGE TIME
: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
•
DEFAULT MESSAGE TIMEOUT
: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.
ENUMERATION
DESCRIPTION
1
Authentication Failed
2
User Lockout
3
FW Upgrade
4
FW Lock
5
Settings Lock
6
Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7
Clear Oscillography command
8
Clear Data Logger command (not applicable to all UR products)
9
Clear Demand Records command (not applicable to all UR products)
10
Clear Energy command (not applicable to all UR products)
11
Clear Unauthorized Access command
12
Clear Teleprotection Counters command (not applicable to all UR products)
13
Clear All Relay Records command
14
Role Log in
15
Role Log off
DISPLAY
PROPERTIES
LANGUAGE:
English
Range: English; English, French; English, Russian;
English, Chinese
(range dependent on order code)
MESSAGE
FLASH MESSAGE
TIME: 1.0
s
Range: 0.5 to 10.0 s in steps of 0.1
MESSAGE
DEFAULT MESSAGE
TIMEOUT: 300 s
Range: 10 to 900 s in steps of 1
MESSAGE
DEFAULT MESSAGE
INTENSITY: 25 %
Range: 25%, 50%, 75%, 100%
Visible when a VFD is installed
MESSAGE
SCREEN SAVER
FEATURE: Disabled
Range: Disabled, Enabled
Visible when an LCD is installed
MESSAGE
SCREEN SAVER WAIT
TIME: 30 min
Range: 1 to 65535 min. in steps of 1
Visible when an LCD is installed
MESSAGE
CURRENT CUT-OFF
LEVEL: 0.020 pu
Range: 0.002 to 0.020 pu in steps of 0.001
MESSAGE
VOLTAGE CUT-OFF
LEVEL: 1.0 V
Range: 0.1 to 1.0 V secondary in steps of 0.1
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...