GE Multilin
G60 Generator Protection System
5-123
5 SETTINGS
5.4 SYSTEM SETUP
5
c) CALIBRATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PHASOR MEASUREMENT UNIT 1
PMU 1 (to 4)
CALIBRATION
This menu contains user angle and magnitude calibration data for the phasor measurement unit (PMU). This data is com-
bined with the factory adjustments to shift the phasors for better accuracy.
•
PMU 1 VA... IG CALIBRATION ANGLE
: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
PMU 1
CALIBRATION
PMU 1 VA CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VA CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 VB CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VB CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 VC CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VC CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 VX CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VX CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IA CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IA CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IB CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IB CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IC CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IC CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IG CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IG CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 SEQ VOLT SHIFT
ANGLE: 0°
Range: –180 to 180° in steps of 30
MESSAGE
PMU 1 SEQ CURR SHIFT
ANGLE: 0°
Range: –180 to 180° in steps of 30
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...