GE Multilin
G60 Generator Protection System
5-33
5 SETTINGS
5.2 PRODUCT SETUP
5
g) ROUTING
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
ROUTING 1(6)
A default route and a maximum number of six static routes can be configured.
The default route is used as the last choice when no other route towards a given destination is found.
Configure the network IP and subnet settings before configuring the routing settings.
ADDING AND DELETING STATIC ROUTES
Host routes are not supported at present.
The routing table configuration is available on the serial port and front panel. This is a deliberate decision, to avoid loss of
connectivity when remotely configuring the UR.
By default the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This is equivalent to saying that the
static routes are not configured. When the destination address is 127.0.0.1, the mask and gateway must be also kept on
default values.
By default, the value of the route gateway address is 127.0.0.1. This means the default route is not configured.
To add a route:
1.
Use any of the static network route entries numbered 1 to 6 to configure a static network route. Once a route destina-
tion is configured for any of the entries 1 to 6, that entry becomes a static route and it must meet all the rules listed in
the next section, General Conditions to be Satisfied by Static Routes.
2.
To configure the default route, enter a default gateway address. Once a default gateway address is configured, it must
be validated against condition 2 of the General Conditions to be Satisfied by Static Routes.
To delete a route:
1.
Replace the route destination with the default loopback address (127.0.0.1). When deleting a route, the mask and
gateway must be also brought back to default values.
2.
Delete the default route by replacing the default gateway with the default value 127.0.0.1.
GENERAL CONDITIONS TO BE SATISFIED BY STATIC ROUTES
The following rules are validated internally:
•
The route mask has IP mask format. In binary this needs to be a set of contiguous bits of 1 from left to right, followed
by one or more contiguous bits of 0.
IPV4 ROUTING
TABLE
IPV4 DEFAULT ROUTE
MESSAGE
IPV4 STATIC
NETWORK ROUTE 1
↓
MESSAGE
IPV4 STATIC
NETWORK ROUTE 6
IPV4 DEFAULT ROUTE
GATEWAY ADDRESS
127.0.0.1
Range: Standard IPV4 unicast address format
IPV4 STATIC
NETWORK ROUTE 1
RT1 DESTINATION:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
RT1 NET MASK:
255.0.0.0
Range: Standard IPV4 subnet mask format
MESSAGE
RT1 GATEWAY:
127.0.0.1
Range: Standard IPV4 unicast address format
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...