GE Multilin
G60 Generator Protection System
2-19
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
BREAKER FAILURE
Mode:
1-pole, 3-pole
Current supervision:
phase, neutral current
Current supv. pickup:
0.001 to 30.000 pu in steps of 0.001
Current supv. dropout:
97 to 98% of pickup
Current supv. accuracy:
0.1 to 2.0
×
CT rating: ±0.75% of reading or ±2% of rated
(whichever is greater)
above 2
×
CT rating:
±2.5% of reading
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
BREAKER FLASHOVER
Operating quantity:
phase current, voltage and voltage differ-
ence
Pickup level voltage:
0 to 1.500 pu in steps of 0.001
Dropout level voltage:
97 to 98% of pickup
Pickup level current:
0 to 1.500 pu in steps of 0.001
Dropout level current:
97 to 98% of pickup
Level accuracy:
±0.5% or ±0.1% of rated, whichever is
greater
Pickup delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±42 ms, which-
ever is greater
Operate time:
<42 ms at 1.10
×
pickup at 60 Hz
SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference:
0 to 100
°
in steps of 1
Max freq. difference:
0.00 to 2.00 Hz in steps of 0.01
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
POWER SWING DETECT
Functions:
Power swing block, Out-of-step trip
Characteristic:
Mho or Quad
Measured impedance:
Positive-sequence
Blocking / tripping modes: 2-step or 3-step
Tripping mode:
Early or Delayed
Current supervision:
Pickup level:
0.050 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Fwd / reverse reach (sec.
Ω
): 0.10 to 500.00
Ω
in steps of 0.01
Left and right blinders (sec.
Ω
): 0.10 to 500.00
Ω
in steps of 0.01
Impedance accuracy:
±5%
Fwd / reverse angle impedances: 40 to 90° in steps of 1
Angle accuracy:
±2°
Characteristic limit angles: 40 to 140° in steps of 1
Timers:
0.000 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
ACCIDENTAL ENERGIZATION
Operating condition:
Overcurrent
Arming condition:
Undervoltage and/or Machine Offline
Overcurrent:
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from
0.1 to 2.0
×
CT rating
Undervoltage:
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading 10 to 208 V
Operate Time:
<30 ms at 1.10
×
pickup at 60 Hz
LOSS OF EXCITATION
Operating condition:
Positive-sequence impedance
Characteristic:
2 independent offset mho circles
Center:
0.10 to 300.0
Ω
(sec.) in steps of 0.01
Radius:
0.10 to 300.0
Ω
(sec.) in steps of 0.01
Reach accuracy:
±3%
Undervoltage supervision
Level:
0.000 to 1.250 pu in steps of 0.001
Accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±20 ms, which-
ever is greater
Operate time:
<50 ms
THERMAL OVERLOAD PROTECTION
Thermal overload curves: IEC 255-8 curve
Base current:
0.20 to 3.00 pu in steps of 0.01
Overload (
k
) factor:
1.00 to 1.20 pu in steps of 0.05
Trip time constant:
0 to 1000 min. in steps of 1
Reset time constant:
0 to 1000 min. in steps of 1
Minimum reset time:
0 to 1000 min. in steps of 1
Timer accuracy (cold curve): ±100 ms or 2%, whichever is greater
Timer accuracy (hot curve): ±500 ms or 2%, whichever is greater
for
I
p
< 0.9 ×
k
×
I
b
and I / (
k
×
I
b
) > 1.1
RTD PROTECTION
Pickup:
1 to 249°C in steps of 1
Dropout level:
2°C of pickup
Timer accuracy:
<1 s
Elements:
trip and alarm
REMOTE RTD PROTECTION
Pickup level:
1 to 200°C
Dropout level:
2°C of pickup
Time delay:
<10 s
Elements:
trip and alarm
TRIP BUS (TRIP WITHOUT FLEXLOGIC)
Number of elements:
6
Number of inputs:
16
Operate time:
<2 ms at 60 Hz
Timer accuracy:
±3% or 10 ms, whichever is greater
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...