6-28
G60 Generator Protection System
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
6.4RECORDS
6.4.1 USER-PROGRAMMABLE FAULT REPORTS
PATH: ACTUAL VALUES
RECORDS
USER-PROGRAMMABLE FAULT REPORT
This menu displays the user-programmable fault report actual values. See the
User-Programmable Fault Report
section in
chapter 5 for additional information on this feature.
6.4.2 EVENT RECORDS
PATH: ACTUAL VALUES
RECORDS
EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. See the
COMMANDS
CLEAR RECORDS
menu for clearing event records.
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
6.4.3 OSCILLOGRAPHY
PATH: ACTUAL VALUES
RECORDS
OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
CYCLES PER RECORD
value is calculated to account for the fixed amount of data storage for oscillography. See the
Oscillog-
raphy
section of chapter 5 for additional details.
USER-PROGRAMMABLE
FAULT REPORT
NEWEST RECORD
NUMBER: 0
MESSAGE
LAST CLEARED DATE:
2002/8/11 14:23:57
MESSAGE
LAST REPORT DATE:
2002/10/09 08:25:27
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
↓
MESSAGE
EVENT: 3
POWER ON
EVENT 3
DATE: 2000/07/14
MESSAGE
EVENT: 2
POWER OFF
EVENT 3
TIME: 14:53:00.03405
MESSAGE
EVENT: 1
EVENTS CLEARED
Date and Time Stamps
OSCILLOGRAPHY
FORCE TRIGGER?
No
Range: No, Yes
MESSAGE
NUMBER OF TRIGGERS:
0
MESSAGE
AVAILABLE RECORDS:
0
MESSAGE
CYCLES PER RECORD:
0.0
MESSAGE
LAST CLEARED DATE:
2000/07/14
15:40:16
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...