GE Multilin
G60 Generator Protection System
B-37
APPENDIX B
B.4 MEMORY MAPPING
B
5F54
Frequency Out-Of-Band Accumulator Time Limit Array (7
items)
1 to 65535
sec
1
F001
200
5F5B
Frequency Out-Of-Band Accumulator Time Preset Array (7
items)
0 to 65535
sec
1
F001
0
5F62
Frequency Out-Of-Band Accumulator Upper Frequency
Array (7 items)
20 to 70
Hz
0.01
F001
6000
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
0 to 4294967295
---
1
F300
0
5F7D
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F7E
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Stator Differential (Read/Write Grouped Setting)
6420
Stator Differential Function
0 to 1
---
1
F102
0 (Disabled)
6421
Stator Differential Pickup
0.05 to 1
pu
0.001
F001
100
6422
Stator Differential Slope 1
1 to 100
%
1
F001
10
6423
Stator Differential Slope 2
1 to 100
%
1
F001
80
6424
Stator Differential Break 1
1 to 1.5
pu
0.01
F001
115
6425
Stator Differential Break 2
1.5 to 30
pu
0.01
F001
800
6426
Stator Differential Block
0 to 4294967295
---
1
F300
0
6428
Stator Differential Targets
0 to 2
---
1
F109
0 (Self-reset)
6429
Stator Differential Events
0 to 1
---
1
F102
0 (Disabled)
642A
Stator Differential Line End Source
0 to 5
---
1
F167
0 (SRC 1)
642B
Stator Differential Neutral End Source
0 to 5
---
1
F167
0 (SRC 1)
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 modules)
6440
Negative Sequence Overvoltage Function
0 to 1
---
1
F102
0 (Disabled)
6441
Negative Sequence Overvoltage Source
0 to 5
---
1
F167
0 (SRC 1)
6442
Negative Sequence Overvoltage Pickup
0 to 1.25
pu
0.001
F001
300
6443
Negative Sequence Overvoltage Pickup Delay
0 to 600
s
0.01
F001
50
6444
Negative Sequence Overvoltage Reset Delay
0 to 600
s
0.01
F001
50
6445
Negative Sequence Overvoltage Block
0 to 4294967295
---
1
F300
0
6447
Negative Sequence Overvoltage Target
0 to 2
---
1
F109
0 (Self-reset)
6448
Negative Sequence Overvoltage Events
0 to 1
---
1
F102
0 (Disabled)
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Overfrequency (Read/Write Setting) (4 modules)
6470
Overfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
6471
Overfrequency 1 Block
0 to 4294967295
---
1
F300
0
6473
Overfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
6474
Overfrequency 1 Pickup
20 to 65
Hz
0.01
F001
6050
6475
Overfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
500
6476
Overfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
500
6477
Overfrequency 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6478
Overfrequency 1 Events
0 to 1
---
1
F102
0 (Disabled)
6479
Reserved (4 items)
0 to 1
---
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...