GE Multilin
G60 Generator Protection System
5-133
5 SETTINGS
5.4 SYSTEM SETUP
5
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
90-5 AGGR 1 CONFIGU-
RATION
•
PMU AGGREGATOR1 PROTOCOL
: This setting selects if the IEEE C37.118 or IEC 61850 standard is used.
•
PMU AGGREGATOR1 IDCODE
: Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output
stream, this identifies the ID of the aggregator - which is only used if there is more than 1 PMU mapped into an aggre-
gator.
•
PMU AGGREGATOR1 PMU1
: If set to “Yes” aggregator 1 includes the PMU1 data set in the reporting data stream.
AGGREGATOR1 will not include PMU1 data set in the report if set to “No”.
C37.118 AGGREGATOR 1 CONFIGURATION
•
PMU AGGREGATOR1: TCP PORT
: This setting selects the TCP port number to be used by this aggregator for net-
work reporting. All ports, even those of unused aggregators, must be valid and unique to avoid port number collisions.
•
PMU AGGREGATOR1 UDP PORT
: This setting selects the UDP port number to be used by this aggregator for net-
work reporting. All ports, even those of unused aggregators, must be valid and unique to avoid port number collisions.
•
PMU AGGREGATOR1 PDC CONTROL
: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in table 2. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is re-started. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
90-5 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
NAME:
Range: 56 character ASCII text
Default: Blank
MESSAGE
PMU AGGREGATOR1:
PORT: 1
Range: 1, 2, 3
Default: 1
MESSAGE
PMU AGGREGATOR 1:
UDP PORT: 102
Range: 1 to 65534 in steps of 1
Default: 102
MESSAGE
PMU AGGREGATOR 1:
NUMBER OF ASDUs: 1
Range: 1 to 4
Default: 1
Table 5–12: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
ELEMENT:
Synchrophasor, phasor data,
concentrator
AGTR1 PDC CNTRL 1
Phasor data concentrator asserts control bit 1, as
received via the network.
as above
AGTR1 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network.
as above
AGTR1 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network.
↓
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network.
as above
AGTR2 PDC CNTRL 1
Phasor data concentrator asserts control bit 1 as
received via the network
as above
AGTR2 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR2 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network.
↓
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network.
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...