GEK-106310AB
F650 Digital Bay Controller
H-19
APPENDIX H
H.1 FACTORY DEFAULT SETTINGS
H
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G >BOARD H>BOARD J
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
I/O board type (available only for CIO
modules)
I/O Board Type_
X
NONE
N/A
[NONE,
16 INP + 8OUT,
8 INP + 8OUT + SUPV
32 INP
16 INP + 8 ANA]
Input activation voltage threshold
Group A
Voltage Threshold
A_
X
80
1 V
[10 : 230]
Input activation voltage threshold
Group B
Voltage Threshold
B
_X
80
1 V
[10 : 230]
Input activation voltage threshold
Group C
Voltage Threshold
C_
X
80
1 V
[10 : 230]
Input activation voltage threshold
Group D
Voltage Threshold
D
_X
80
1 V
[10 : 230]
Debounce time for Group A
Debounce Time A
_X
15
1 ms
[1 : 50]
Debounce time for Group B
Debounce Time B
_X
15
1 ms
[1 : 50]
Debounce time for Group C
Debounce Time C
_X
15
1 ms
[1 : 50]
Debounce time for Group D
Debounce Time D
_X
15
1 ms
[1 : 50]
Input type
Input Type_
X
_CC
Y
(CC
Y
)
POSITIVE
N/A
[POSITIVE-EDGE,
NEGATIVE-EDGE,
POSITIVE,
NEGATIVE]
Input signal time delay
Delay Input
Time_
X
_CC
Y
(CC
Y
)
0
1 ms
[0 : 60000]
Output logic type
Output Logic_
X
_0
Z
POSITIVE
N/A
[POSITIVE,
NEGATIVE]
Output type
Output Type_
X
_0
Z
NORMAL
N/A
[NORMAL,
PULSE,
LATCH]
Output pulse length
Pulse Output
Time_
X
_0
Z
10000
1 ms
[0 : 60000]
Analog Inputs Range
Range_
X
_0
Z
NONE
N/A
[NONE,
-1 to 0mA,
0 to 1 mA,
-1 to 1 mA,
0 to 5 mA,
0 to 10 mA]
Minimum Value
Min_Value_
X
_0
Z
0.00
0.01
[ -9999.99 : 9999.99]
Maximum Value
Max_Value_
X
_0
Z
0.00
0.01
[ -9999.99 : 9999.99]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin F650
Страница 9: ...8 F650 Digital Bay Controller GEK 106310AB TABLE OF CONTENTS ...
Страница 147: ...4 74 F650 Digital Bay Controller GEK 106310AB 4 3 WEB SERVER 4 HUMAN INTERFACES SETTINGS ACTUAL VALUES 4 ...
Страница 323: ...5 176 F650 Digital Bay Controller GEK 106310AB 5 13 IEC 60870 5 103 PROTOCOL CONFIGURATION 5 SETTINGS 5 ...
Страница 443: ...7 74 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 Figure 7 21 ...
Страница 457: ...7 88 F650 Digital Bay Controller GEK 106310AB 7 3 IEC 61850 CONFIGURATOR 7 IEC 61850 PROTOCOL 7 ...
Страница 513: ...10 28 F650 Digital Bay Controller GEK 106310AB 10 18 THERMAL IMAGE ELEMENT 49 10 COMMISSIONING 10 ...
Страница 529: ...12 6 F650 Digital Bay Controller GEK 106310AB 12 4 RELAY CONFIGURATION 12 FREQUENTLY ASKED QUESTIONS 12 ...
Страница 569: ...A 36 F650 Digital Bay Controller GEK 106310AB A 1 LOGIC OPERANDS APPENDIX A A ...
Страница 735: ...C 24 F650 Digital Bay Controller GEK 106310AB C 8 ANALOG INPUTS APPENDIX C C ...
Страница 743: ...D 8 F650 Digital Bay Controller GEK 106310AB D 5 IEC 60870 5 104 POINT LIST APPENDIX D D ...
Страница 755: ...F 10 F650 Digital Bay Controller GEK 106310AB F 1 IEC 60870 5 103 PROTOCOL APPENDIX F F ...
Страница 766: ...GEK 106310AB F650 Digital Bay Controller G 11 APPENDIX G G 1 FACTORY DEFAULT LOGIC G ...
Страница 767: ...G 12 F650 Digital Bay Controller GEK 106310AB G 1 FACTORY DEFAULT LOGIC APPENDIX G G ...
Страница 801: ...I 2 F650 Digital Bay Controller GEK 106310AB I 1 GE MULTILIN WARRANTY APPENDIX I I ...